SUPERSCAN INFRARED PRESENCE BEAM INSTRUCTION MANUALFOR INDUSTRIAL APPLICATIONS We can be reached from anywhere in the world: US &a
75.1035 V1 Feb 2001 Page 2 of 8 SUPERSCAN ACTIVE INFRARED PRESENCE BEAM The SuperScan safety detector is a presence detection system that is pri
75.1035 V1 Feb 2001 Page 3 of 8 COMMON INDUSTRIAL APPLICATIONS: DOORS WHERE OVERHEAD ACTIVATION SENSORS ARE NOT ABLE TO BE MOUNTED: For applica
75.1035 V1 Feb 2001 Page 4 of 8 SUPERSCAN INSTALLATION PROCEDURES **B.E.A. sensors, as with all automatic door equipment, should be set up and ins
75.1035 V1 Feb 2001 Page 5 of 8 ON SITE ADJUSTMENTS 1. Position of the Master and Slave Modules in the Aluminum Extrusion NOTE:
75.1035 V1 Feb 2001 Page 6 of 8 Adjustment of the Detection Distance Use the procedure listed below to adjust each detector in order to obtain d
75.1035 V1 Feb 2001 Page 7 of 8 PASSIVE RELAY: The relay is de-energized when the detector is at rest 1. NORMALLY OPEN: Use NO & COM termina
75.1035 V1 Feb 2001 Page 8 of 8 SuperScan Terminals Wiring Connections for Industrial Use 1 NOTE USED 2 NOT USED 3 NOT USED 4 (NO) In the rel